← All Wires & Cables
HFFR SERIES
Firenetic 6762
Zero Halogen Fire Retardant
Halogen-free fire retardant insulated single-core unsheathed copper cable up to 1100V AC with transparent, non-toxic and minimal smoke during fire.
Special Polymer / HFFRInsulation
70°CTemperature Rating
ExcellentFlame Retardancy
< 0.5%Halogen Gas
Available colours: Red, Blue, Green, Yellow, Black, White, Grey
Packing: 90 metres (approx. 100 yards) in protective cartons
TECHNICAL DATA
Available conductor sizes
| Nominal Area | Strands | Insulation | Overall Dia. | Conduit / Trunking | Clipped / Tray | Resistance @20°C |
|---|---|---|---|---|---|---|
| 1.0 sq. mm | 14/0.3 mm | 0.7 mm | 2.7 mm | 11 A | 12 A | 18.10 Ω |
| 1.5 sq. mm | 22/0.3 mm | 0.7 mm | 3.0 mm | 13 A | 16 A | 12.10 Ω |
| 2.5 sq. mm | 36/0.3 mm | 0.8 mm | 3.6 mm | 18 A | 22 A | 7.41 Ω |
| 4.0 sq. mm | 56/0.3 mm | 0.8 mm | 4.1 mm | 24 A | 29 A | 4.95 Ω |
| 6.0 sq. mm | 84/0.3 mm | 0.8 mm | 4.6 mm | 31 A | 37 A | 3.30 Ω |
Technical data is indicative and may be revised. Conductor strand details are governed by conductor resistance; confirm current application requirements before installation.